23-50 Energy Log Resolution
Option: Function:
Week, or [2] Day of Month. The counters
contain the logging data from the
programmed date/time for start
(parameter 23-51 Period Start) and the
numbers of hours/days as programmed for
(parameter 23-50 Energy Log Resolution).
The logging starts on the date programmed
in parameter 23-51 Period Start and continues
until 1 day/week/month has passed. The
counters contain data for 1 day, 1 week, or 5
weeks back in time, and up to the actual
time.
The logging starts at the date programmed
in parameter 23-51 Period Start. In all cases,
the period split refers to operating hours
(time where frequency converter is powered
up).
[0] Hour of Day
[1] Day of Week
[2] Day of
Month
[5] * Last 24
Hours
[6] Last 7 Days
[7] Last 5
Weeks
23-51 Period Start
Range: Function:
Size
related*
[ 0 -
0 ]
NOTICE
When mounting VLT
®
Analog I/O option
MCB 109, a battery back-up of the date
and time is included.
Set the date and time at which the energy log
starts updating the counters. First, data is
stored in counter [00] and start at the time/
date programmed in this parameter.
Date format depends on setting in
parameter 0-71 Date Format and time format
on setting in parameter 0-72 Time Format.
23-53 Energy Log
Array [31]
Range: Function:
0* [0 -
4294967295 ]
NOTICE
All counters are automatically reset
when changing the setting in
parameter 23-50 Energy Log Resolution.
At overow, the update of the counters
stops at maximum value.
23-53 Energy Log
Array [31]
Range: Function:
NOTICE
When mounting VLT
®
Analog I/O Option
MCB 109 option card, a battery back-up
of the date and time is included.
Array with several elements equal to the
number of counters ([00]-[xx] below parameter
number in display). Press [OK] and step
between elements with [
] and [
].
Array elements:
130BA280.11
23-5*
23-5*
23-5*
23-5*
23-5*
23-5*
23-5*
23-53 Ener gy met er
(00)
Ener gy met er
Ener gy met er
23-53 Ener gy met er
(01)
23-53 Ener gy met er
(02)
Ener gy met er
23-53 Ener gy met er
(03)
Ener gy met er
23-53 Ener gy met er
(04)
Ener gy met er
23-53 Ener gy met er
(05)
Ener gy met er
23-53 Ener gy met er
(06)
Ener gy met er
Illustration 3.76 Energy Log
Data from the latest period is stored in the
counter with the highest index.
At power-down, all counter values are stored
and resumed at next power-up.
23-54 Reset Energy Log
Option: Function:
Select [1] Do reset to reset all values in the
energy log counters shown in
parameter 23-53 Energy Log. After pressing OK,
the setting of the parameter value automatically
changes to [0] Do not reset.
[0] * Do not
reset
[1] Do reset
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 197
3 3

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals