5
VFD-L Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-21
Note: Multi-function Input Terminal M0 does not have its own parameter designation. M0
must be used in conjunction with M1 to operate two and three wire control.
d3: Three Wire Control:
Restricted to Pr.4-04 control terminals M0, M1, M2.
STOP
RUN
RUN/FWD
M0 Run command, Runs when "close"
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
"Open": FWD Run
"Close": REV Run
GND
Note: When value d3 is selected for Pr. 4-04, this will over ride any value entered in
Pr.4-05, since Pr.4-05 must be used for three wire control as shown above.
d4, d5 External Faults:
Parameter values d4, d5 programs Multi-Function Input Terminals: M1 (Pr.4-04), M2
(Pr.4-05) or M3 (Pr.4-06) to be External Fault (E.F.) inputs.
GND
E.F.(N.O.)
setting by d4
E.F(N.C.)
setting by d5
Mx "Close": Operation available.
Mx "Open":Operation available.
When an External Fault input signal is received, the AC drive will stop all output and
display
³
E.F.
´
on Digital Keypad, the motor will free run. Normal operation can resume
after the External Fault is cleared and the AC drive is reset.
d6 External Reset:
Parameter value d6 programs a Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05)
or M3 (Pr.4-06) to be an External Reset.
GND
RESET
setting by d6
Mx "Close": Operation available

Table of Contents

Other manuals for Delta VFD-L Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-L Series and is the answer not in the manual?

Delta VFD-L Series Specifications

General IconGeneral
Control MethodV/F Control
Output Voltage0 to Input Voltage
Cooling MethodFan Cooling
Enclosure RatingIP20
Overload Capacity150% for 60 seconds
ProtectionOver-voltage, Over-current, Overheat, Under-voltage, Short circuit
Braking UnitBuilt-in
Operating Temperature-10°C to 50°C (14°F to 122°F)
Digital Inputs5 programmable digital inputs
Analog Input0-10V, 4-20mA
Communication InterfaceRS-485 (Modbus)
Storage Temperature-20°C to 60°C (-4°F to 140°F)
Humidity90% RH, non-condensing
AltitudeUp to 1000m without derating
Input Voltage200-240V, 380-480V

Related product manuals