VFD-L Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
9 - 03
odbus Communication Watchdog Timer
Factory Setting: d 0
Settings d0 Disable Unit: 1 sec
d1 to d20 1 to 20 sec
This parameter can be set during operation.
If the Watchdog timer function is enabled, the timer will start counting once the first valid
Modbus communication signal is received after power-up or reset. The timer will reset
to 0 after each valid Modbus communication message is received. If the watchdog timer
reaches the value set in Pr. 9-03, the drive will stop its output and display the message
"CE10" on the digital keypad. This fault can reset by an external terminal, keypad or a
Modbus communication reset command.
9 – 04
ommunication Protocol
actory Setting: d 0
Settings d 0 Modbus ASCII mode, protocol <7,N,2>
d 1 Modbus ASCII mode, protocol <7,E,1>
d 2 Modbus ASCII mode, protocol <7,O,1>
d 3 Modbus ASCII mode, protocol <8,N,2>
d 4 Modbus ASCII mode, protocol <8,E,1>
d 5 Modbus ASCII mode, protocol <8,O,1>
d 6 Modbus RTU mode, protocol <8,N,2>
d 7 Modbus RTU mode, protocol <8,E,1>
d 8 Modbus RTU mode, protocol <8,O,1>
This parameter can be set during operation.
1.Computer Control
There is a built-in RS-485 serial interface, marked (RJ-11 Jack) on the control
terminal block, for VFD Series. The pins are defined below:
Each VFD-L AC drive has a pre-assigned communication address specified by Pr.
(9-00). The computer then controls each AC drive according to its communication
address.