CHAPTER 7 Troubleshooting and Fault Information
The VFD-L AC drive has a comprehensive fault diagnostic system that includes
several different alarms and fault messages. Once a fault is detected, the
corresponding protective functions will be activated. The following faults are
displayed on the AC drive digital keypad. The six most recent faults can be
read on the digital keypad display by viewing Pr.6-07 to Pr.6-12.
NOTE: Faults can be cleared by a reset from the keypad or Input Terminal.
Common Problems and Solutions:
Fault
Name
Fault Descriptions
Corrective Actions
The AC drive detects an
abnormal increase in
current.
1. Check whether the motors horsepower
corresponds to the AC drive output
power.
2. Check the wiring connections between
the AC drive and motor for possible
short circuits.
3. Increase the Acceleration time.
4. Check for possible excessive loading
conditions at the motor.
5. If there are any abnormal conditions
when operating the AC drive after
short-circuit being removed, it should
be sent back to manufacturer.
The AC drive detects
that the DC bus voltage
has exceeded its
maximum allowable
value.
1. Check whether the input voltage falls
within the rated AC drive input voltage.
2. Check for possible voltage transients.
3. Bus over-voltage may also be caused
by motor regeneration. Either increase
the decel time or add an optional
braking resistor.
4. Check whether the required braking
power is within the specified limits.

Table of Contents

Other manuals for Delta VFD-L Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-L Series and is the answer not in the manual?

Delta VFD-L Series Specifications

General IconGeneral
Control MethodV/F Control
Output Voltage0 to Input Voltage
Cooling MethodFan Cooling
Enclosure RatingIP20
Overload Capacity150% for 60 seconds
ProtectionOver-voltage, Over-current, Overheat, Under-voltage, Short circuit
Braking UnitBuilt-in
Operating Temperature-10°C to 50°C (14°F to 122°F)
Digital Inputs5 programmable digital inputs
Analog Input0-10V, 4-20mA
Communication InterfaceRS-485 (Modbus)
Storage Temperature-20°C to 60°C (-4°F to 140°F)
Humidity90% RH, non-condensing
AltitudeUp to 1000m without derating
Input Voltage200-240V, 380-480V

Related product manuals