VFD-L Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-20
Parameters & Functions table:
Valu
e
Function Value
Function
d 0
(
input not used) d11
F
irst or Second Accel/Decel Time
S
election
d 1
M
0: FWD / STOP
M
1: REV / STOP
d12
E
xternal Base Block (N.O.)
(
Normally Open Contact Input)
d 2
M
0: RUN / STOP
M
1: FWD / REV
d13
External Base Block (N.C.)
(
Normally Close Contact Input)
d 3
3
-Wire Operation Control mode
(
M0,M1,M2)
d14
I
ncrease Master Frequency
d 4
E
xternal Fault ( Normally Open) d15
D
ecrease Master Frequency
d 5
E
xternal Fault ( Normally Closed )
d16
R
un PLC Program
d 6
E
xternal Reset d17
P
ause PLC Program
d 7
M
ulti-Step Speed Command 1 d18
C
ounter Trigger Signal
d 8
M
ulti-Step Speed Command 2 d19
C
ounter Reset
d 9
J
og operation d20
S
elect ACI/deselect AVI
d10
A
ccel/Decel Speed Inhibit
Explanations:
d0 Parameter Disable:
Enter value (d0) to disable any Multi-Function Input Terminal: M0, M1 (Pr.4-04), M2
(Pr.4-05) or M3 (Pr.4-06).
Note:The purpose of this function is to provide isolation for unused Multi-Function Input
Terminals. Any unused terminals should be programmed to d0 to insure they have
no effect on drive operation.
d1:Two wire operation:
Restricted to Pr.4-04 and external terminals M0, M1.
FWD/STOP
REV/STOP
M0 "Open": Stop, "Close": FWD Run
M1 "Open": Stop, "Close":REV Run
GND
d2: Two wire operation:
Restrict to Pr. 4-04 and external terminals M0, M1.
RUN/STOP
REV/FWD
M0 "Open": Stop, "Close": Run
M1 "Open": FWD, "Close":REV
GND