Digital Monitoring Products XR500 Series Canadian Programming Guide
12
COMMUNICATION
3.29
ALARM YES
Alarm Reports
This prompt displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Alarm Reports. Default is Yes.
NO YES FIRE
When YES is selected, the following reports are sent to the receiver for all zone
types:
•Alarm •Bypass •Reset •Restore
When FIRE is selected, the following reports are sent for Fire, Fire Verify and
Supervisory Zones:
•Alarm •Bypass •Reset •Restore
3.30
SPV/TRBL YES
Supervisory/Trouble Reports
This prompt displays when the Path Type is Primary. All backup paths within the
groupfollowthesameprogrammingforSupervisory/TroubleReports.DefaultisYes.
NO YES FIRE
When YES is selected, the following reports are sent for all zone types:
•Trouble •LowBattery •Missing •Fault
•Restorals •SystemTroubles •SystemRestoral
When FIRE is selected, the following reports are sent for Fire, Fire Verify, and
Supervisory Zones:
•Trouble •LowBattery •Missing •Fault
•Restorals •SystemTroubles •SystemRestoral
3.31
O/C USER NO YES
Opening/Closing and User Reports
This prompt displays when the Path Type is Primary. All backup paths within the
groupfollowthesameprogrammingforOpening/ClosingandUserReports.Default
is Yes.
When YES is selected, the following reports by user are sent to this receiver.
•Opening •Codechanges(includingadding,deleting,changing)
•Closing •Schedulechanges(temporary,permanent,shift)
•Bypass •Holidaydatechanges
•Reset
3.32
DOOR ACS YES
Door Access Report
This prompt displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Door Access Reports. Default is Deny.
NO YES DENY
SelectYEStoenableDoorAccessGrantedandDeniedreportstothisreceiver
wheneveradooraccessisgrantedtoauser.TheDoorAccessGrantedreportis
only sent if the keypad number has also been selected in Access Keypads under the
SYSTEM REPORTS programming.
Select DENY to enable Door Access Denied reports only to this receiver when a door
access is denied to a user.
3.33
PANIC TST NO YES
Panic Test (XR500N/XR500E only)
YESallowsthepaniczonetestvericationandfailureresultstobesenttothe
central station receiver. NO disables the panic test report. The default setting is
NO.Thesystemteststart,stop,paniczoneverication,andpaniczonefailure
messages sent to the central station and the trips count operation are the same as
used under the Walk Test. See Using the Walk Test section in the Appendix.
3.33
SEND COMM TRBL:
Send Communication Trouble
NO YES
This prompt displays for each path and determines if and how communication
trouble on the path is sent to the receiver. A trouble message indicates both the
path number and communication type that failed. Default is Yes.
3.34
SEND PATH INFO:
Send Path Information
NO YES
This prompt displays for each path and if YES, each panel message includes path
information such as path number, communication type, and path type. Default is No.

Table of Contents

Other manuals for DMP Electronics XR500 SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics XR500 SERIES and is the answer not in the manual?

DMP Electronics XR500 SERIES Specifications

General IconGeneral
BrandDMP Electronics
ModelXR500 SERIES
CategoryControl Panel
LanguageEnglish

Related product manuals