EasyManuals Logo

DMP Electronics XR500 SERIES Programming Guide

DMP Electronics XR500 SERIES
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Digital Monitoring Products XR500 Series Canadian Programming Guide
18
DEVICE SETUP
• DoorScheduleschangesareallowedfordevicesthathaveamatchingarea(s)
asdenedinDeviceAccessAreas
• DoorOn/OffMenuoperationisallowedfordevicesthathaveamatchingarea(s)
asdenedinDeviceAccessAreas
Note:Theprevioususeractionsalsorequirethematchingarea(s)beprogrammedin
UserProle:Arm/Disarmarea(s).
Status Display Allowed
Whenanarea(s)ischosen,thefollowingdisplaysareallowed:
• ArmedStatusoftheselectedarea(s)
• ZoneAlarmsandtroublesforburglary(NT,DY,EX,A1,A2)typezonesassignedto
theselectedarea(s)
• LatetoClosestatusoftheselectedarea(s)
• ZoneStatus(normal/fault)ofzonesthatareassignedtotheselectedarea(s)
Options and Actions Not Affected
The following options are not affected by the Display Areas operation. The User
Code authority level controls access to these items.
• SensorResetMenu •OutputsOn/OffMenu • SystemStatusMenu
• SystemTest/PanicTest •UserProles • ForgiveAnti-Passback
• ServiceRequest •SetSystemTimeandDate
• FireDrill •DisplayEvents
• 24-hourzonesdisplayatkeypadsbasedonStatusListprogrammingonly
Note:Acommonareaanditsoperationscannotbeassignedtoaspecickeypad.
Display Areas example: When Device 1 has Display Areas set to 20, 21, and 22, it
annunciates troubles and alarms only for zones assigned to those areas.
Whenarming/disarmingfromDevice1,onlyareas20,21,and22maybearmed/
disarmed,evenwhentheUserProlehasauthoritytoarm/disarmothersystemareas.
Exception: Disarming of other areas not selected in Display Areas can be
accomplishedbypresentingacardthathasdisarmingauthorityandmatchingprole
areas with areas assigned in Device Access Areas.
6.9
STRIKE TIME: 5
Strike Time
This option displays if DOOR is selected as Device Type.
Enter a door access time, between 1 and 250 seconds, during which a keypad or access
control device relay is activated. Magnetic locks or electric door strikes are connected
to the relay and released for the length of the strike time. Default is 5 seconds.
Enter0(zero)toactivatethedevicerelaywithatoggleaction.Thisallowstheuser
to activate or deactivate the device relay each time a valid user code is entered.
The device relay is activated or deactivated until a user code is entered again.
Note:TheRequesttoExitdooraccesstimeofakeypadorModel733Wiegand
Interface Module is not affected by this selection. It remains at 5 seconds.
6.10
STRIKE DELAY: 0
Strike Delay
This option displays if DOOR is selected as Device Type.
Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is entered
or a card read occurs. When a valid code or card read or code is received, the activation
of the door strike is delayed for the number of minutes programmed. The standard door
strike message is sent to the Central Station receiver and logged in the Display Events at
the time of card read or code entry and is not delayed. During this delay, all subsequent
codes entered or cards presented to the reader for a door strike are ignored and no
recordoftheattemptisstored.Enter0(zero)todisable.Defaultis0(zero).
6.11
FIRE EXIT NO YES
Fire Exit Release
Select YES to allow the door access relay at this address to be released whenever
FirepanickeysarepressedoraFireorFireVerifyzonealarmisintheStatusList.
The relay is reset whenever a Sensor Reset is performed to remove all Fire and Fire
VerifyzonealarmsfromtheStatusList.SelectNO to not allow the door access relay
at this address to be released.
6.12
OUT GROUP NO YES
Output Group
Select YEStoallowtheoutputgroup(relays)assignedtotheuserproletoturnON
when the device relay is activated for the programmed strike time. This could be
used to operate an elevator control. Default is NO. See the User Proles section in
theAppendixofthisdocumentformoreinformationaboutproles.

Table of Contents

Other manuals for DMP Electronics XR500 SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics XR500 SERIES and is the answer not in the manual?

DMP Electronics XR500 SERIES Specifications

General IconGeneral
BrandDMP Electronics
ModelXR500 SERIES
CategoryControl Panel
LanguageEnglish

Related product manuals