8
COMMUNICATION
3.9 Check-in Minutes
Enter the number of minutes (3 to 240) between check-in reports for NET
Communication. Check-in reports are a method of supervising the panel for
communication with the receiver for Net communication. Enter 0 (zero) to disable
this feature. The default Check-in Time is 200 minutes.
3.10 Fail Time
Fail Time allows the receiver to miss a dened number of check-ins before logging
that the panel is missing. For example, if checkin is 20 and Fail TIME is 30, the
receiver only indicates a Panel Not Responding after 30 minutes. The Fail TIME must
be equal to or greater than the CHECKIN minutes: If the CHECKIN is 20 minutes, the
FAIL TIME must be 20 or more. The maximum FAIL TIME is 240 minutes. The default
fail TIME is 240 minutes.
3.11 Send Communication Trouble
Enable communication fail notication by selecting YES at COMM TRBL. Select NO to
disable. Default is YES.
When COMM TRBL is YES and the panel detects a failure of communication, the
panel sends an S72 (Comm Trouble) message through a backup communication
method with notication of the failure. If both primary and secondary methods of
communication fail, then two S72 messages will be sent via the third communication
method, if programmed.
When communication is restored, the panel sends an S73 (Comm Restored) message
through the primary communication.
Note: If the primary or secondary communication type is CELL, S72 and S73
messages include the cell signal strength as a -dBm value.
3.12 First GPRS APN
Enter the rst APN (Access Point Name). This allows an access point for cellular
communication and is used to connect to a DNS network. The APN may contain two
lines of 16 characters to equal 32 characters. Default is set to SECURECOM400.
3.13 Second GPRS APN
Enter the second APN (Access Point Name). This works as a backup in case the rst
APN fails. The APN may contain two lines of 16 characters to equal 32 character
Default is set to SECURECOM400.
3.14 Receiver 1 Programming
Allows you to set the options for the rst receiver the XT30/XT50 panel attempts
to contact when sending reports. The XT30/XT50 supports communication to two
receivers.
3.15 Alarm Reports
YES enables Abort, Alarm, Alarm Restoral, Alarm Bell Silenced, Ambush, Exit Error,
and System Recently Armed reports to be sent to this receiver. Default is YES.
3.16 Supervisory/Trouble Reports
YES enables Supervisory, Trouble, Trouble Restoral, Force Armed, Late to Close, and
Fault reports to be sent to this receiver. Default is YES.
3.17 Opening/Closing and User Reports
YES enables Opening/Closing, Door Access, Schedule and Code Changes, Bypass, and
Sensor Reset reports by user to be sent to this receiver. Default is YES.
3.18 Test Report
Enter YES to enable the Recall Test report to be sent to this receiver.
CHECKIN: -
FAIL TIME: -
COMM TRBL NO YES
SECURECOM400
-
FIRST GPRS APN
SECURECOM400
-
SECOND GPRS APN
RECEIVER 1 PROG
ALARM NO YES
SPV/TRBL NO YES
O/C USER NO YES
TEST RPT NO YES