50 XTLtouch Series Programming Guide | Digital Monitoring Products
Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for fire devices.
Wireless Fire Verification
Fire verify may only be used for 1164 smoke detectors.
Battery Standby
For listed applications, the panel must have 24 Hour battery standby operation. The Model XTL+BAT4800 battery should
be used for fire installations.
Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.
False Alarm Reduction Programmable Options ANSI/SIA CP-01-2010
Shipping Defaults and Recommended Programming
SIA CP-01 FEATURE
DESCRIPTION
DMP PROGRAMMING
GUIDE
REQUIREMENT RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
Exit Time Exit Delay Required (Programmable) 45 sec. - 250 sec. 60 Seconds 60 Seconds
Progress Annunciation Prewarn Address Allowed
Individual keypads may be
disabled per zone
All keypads
enabled
All keypads enabled
Exit Time Restart Exit Delay Required Option For re-entry during exit time Enabled Enabled
Auto Stay Arm on Unvacated
Premises
Occupied Premise - See
Install Guide
Required Option (except for
remote arming)
Occupied Premise NO/YES
option
Enabled
Enabled Yes for
Residential Applications
Exit Time and Progress
Annunciation/Disable - for
Remote Arm
Not Available on Remote
Arming
Allowed Option
Progress Annunciation Always
disabled for Remote Arming
Not Available
Remote Arming not
allowed for CP-01
installations.
Entry Delay(s) Entry Delay
Required (Programmable)
Only use Entry Delay 1. Do
not use Entry Delay 2.
30 sec. – 240 Sec. ** 30 Seconds At least 30 Seconds **
Abort Window – for Non-Fire
Zones
Transmit Delay Required Option Disable by zone or zone type
Enabled NT
DY EX Zone
Enabled
Abort Window Time – for Non-
Fire Zones
Transmit Delay Required (Programmable) 20 sec., 30 sec., or 40 sec. ** 30 Seconds At least 20 Seconds **
Abort Annunciation Transmit Delay Required Option
Annunciate that no alarm was
transmitted
Yes Yes
Cancel Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that a Cancel was
transmitted (S49)
Always
Enabled
Yes
Duress Feature
User Code + 1 = Ambush
Code Not Available
Allowed Option
No 1 + derivative of another user
code/no duplicates with other
user codes
Code +1
Always
Disabled
Not Programmable
Cross Zoning Cross Zone Required Option Yes/No Zone Programming No
Enabled using two or
more programmed zones
Programmable Cross Zoning Time Cross Zone Time Allowed 4 sec. - 250 sec. 0 Seconds
Per walk path in protected
premises
Swinger Shutdown Not Available — Always On Required 1-6 trips 2 trips 2 trips
Swinger Shutdown Disable Swinger Bypass Allowed For non-police response zones Yes Enabled (all zones)
Fire Alarm Verification Zone Type Required Option FV Type Zone No
Yes as required (unless
sensors can self verify)
System Test Walk Test Allowed Test all protection devices N/A N /A
Communications Walk Test Not Allowed N/A N/A N /A
* Programming at installation may be subordinate to other listed requirements for the intended application.
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.
Local Bell
All non-fire zones such as Night, Day, Exit, Aux 1 and Aux 2 must be programmed for local bell enabled with a bell cuto time set to a minimum of 6 minutes to provide a cancel
window of 5 minutes or greater. This does not apply to manually operated zone types such as Panic and Emergency.
The requirements are superseded by any requirements for Commercial Burglar, Household Fire Warning, or Household Burglar applications.
Minimum Installation Requirements: SIA CP-01-2010 minimum system installation requirements include an XTLtouch, an 1135 Wireless Siren, and communication to an SCS-1R
receiver.