ChemLogic® CL96 Operating Manual
6.2.a Setup -> Point Setup
When the Point Setup button is touched the screen below appears. The buttons along the top allow selection
of each analyzer that is installed (if not installed the buttons are disabled). Selecting an analyzer with the
button at the top will display the configuration of the corresponding 16 points for the selected analyzer.
Touching anywhere on the row for each point will bring up the screen in 6.2.a.2 which allows each point to be
configured.
Figure 6.2.a.1
For each point the Gas type, alarm levels, name, location, description, K Factor, and enabled/disabled may be
adjusted. Note that changing the K Factor requires a high-level password.
The alarm levels will automatically be adjusted to the default levels when the gas time is changed from the
drop-down menu. Alarm Level 1 must be >= LAL for the selected gas, <= Alarm Level 2, AND <=Full Scale for
the selected gas. Alarm Level 2 must be >= LAL for the selected gas, >=Alarm Level 1, AND <= Full Scale for the
selected gas.