ChemLogic® CL96 Operating Manual
H.2 Profibus
The following information is available on the Profibus/Slave interface. The CL96 Faults/Alarms (Discrete
Outputs)
Token
Description Type
Machine Critical Fault
Machine has critical fault
Boolean
Machine Maintenance Fault
Machine has a maintenance issue
Boolean
Machine Gas Alarm 1
Level 1 Gas Alarm at Least 1 Machine Point
Boolean
Machine Gas Alarm 2
Level 2 Gas Alarm at Least 1 Machine Point
Boolean
Power On
Power is on to Analyzer
Boolean
Each Analyzer Faults/Alarms (Discrete Outputs)
Token
Description Type
Analyzer Critical Fault
This Analyzer has critical fault
Boolean
Analyzer Maintenance Fault
This analyzer has a maintenance issue
Boolean
Analyzer Gas Alarm 1
Level 1 Gas Alarm at Least 1 Point on Analyzer
Boolean
Analyzer Gas Alarm 2
Level 2 Gas Alarm at Least 1 Point on Analyzer
Boolean
Analyzing
Analysis active on Analyzer
Boolean
Each Point Concentration & Alarm Indicators
Token
Description Type
Concentration
Current concentration (*10) for point
Word