ChemLogic® CL96 Operating Manual
H.2.1 Data Format
Default Slave ID: 2 Size (Bytes): 228
Byte #
(Bytes)
Size #
Bytes
Data Description Format
1
4
Connection Status
5
192
Concentration levels for all 96 Points
Conc * 10 (eg. 23 = 2.3 actual conc)
197
2
Analyzer A Alarm Level 1 Indicators
Bit 0 - 15 = Alarm Level 1 points 1-16
199
2
Analyzer A Alarm Level 1 Indicators
Bit 0 - 15 = Alarm Level 1 points 17-32
201
2
Analyzer B Alarm Level 1 Indicators
Bit 0 - 15 = Alarm Level 1 points 1-16
203
2
Analyzer B Alarm Level 1 Indicators
Bit 0 - 15 = Alarm Level 1 points 17-32
205
2
Analyzer C Alarm Level 1 Indicators
Bit 0 - 15 = Alarm Level 1 points 1-16
207
2
Analyzer C Alarm Level 1 Indicators
Bit 0 - 15 = Alarm Level 1 points 17-32
209
2
Analyzer A Alarm Level 2 Indicators
Bit 0 - 15 = Alarm Level 1 points 1-16
211
2
Analyzer A Alarm Level 2 Indicators
Bit 0 - 15 = Alarm Level 1 points 17-32
213
2
Analyzer B Alarm Level 2 Indicators
Bit 0 - 15 = Alarm Level 1 points 1-16
215
2
Analyzer B Alarm Level 2 Indicators
Bit 0 - 15 = Alarm Level 1 points 17-32
217
2
Analyzer C Alarm Level 2 Indicators
Bit 0 - 15 = Alarm Level 1 points 1-16
219
2
Analyzer C Alarm Level 2 Indicators
Bit 0 - 15 = Alarm Level 1 points 17-32
221
2
Faults/Alarms Analyzer A
*See Below
223
2
Faults/Alarms Analyzer B
*See Below
225
2
Faults/Alarms Analyzer C
*See Below
227
2
Faults/Alarms CL96
*See Below
The Fault/Alarms are indicated as follows:
Bit 0 Critical Fault
Bit 1 General Fault
Bit 2 Alarm Level 1
Bit 3 Alarm Level 2
Bit 4 Analysis Active
Bit 5 Power
Bit 7 - Heartbeat
For Analyzer A, B and C the lower 8 bits (0-7) are for the lower analyzer and the upper 8 bits (8-15) are for the
upper analyzer. For the CL96 Fault/Alarms the alarms indicate the status of the entire machine. See Appendix
B for detail on the I/O indicators.
The bits for Alarm Level 1, Alarm Level 2 and all the Fault/Alarms may be affected by the “Energized
Faults/Alarms” setting of the CL96.