ChemLogic® CL96 Operating Manual
Appendix H – Data Communication
H.1 – Ethernet/IP
IMPORTANT: if you move to change the IP address of the CL96 the System must be ‘re-activated’ by DOD
Technologies support before data can be monitored via the Ethernet/IP Slave connection.
H.1.1 Data Format
The Ehternet/IP interface allows remote monitoring of fault/alarm outputs, concentration levels, and fault rest.
You must supply the IP Address of the CL96 to DOD Technologies, INC to configure the Ethernet/IP. The data
is mapped as:
Downlink (From Master to CL96):
Assembly Instance: 102
Size (16-bit Words) : 3
Data Description Format
Bit 0 - Change from 1 to 0 to reset faults
Uplink (From CL96 to Master) :
Assembly Instance: 101
Size (16-bit words) : 114