Figure 10-5: 1-phase Tie Cabinet’s wiring diagram with two UPS units and bypass connected
UPS Module Bypass input X1 Rectifier input F2
Cable A Cable C Fuse 1 Cable B Fuse 2
8 kVA 10 mm² 10 mm² 50 A 2,5 mm² 16 A
10 kVA 10 mm² 10 mm² 50 A 4 mm² 20 A
12 kVA 16 mm² 16 mm² 63 A 6 mm² 25 A
15 kVA 25 mm² 16 mm² 80 A 6 mm² 32 A
TC Module Cable D Cable E Cable F
8 kVA 10 mm² 10 mm² 10 mm²
10 kVA 10 mm² 10 mm² 10 mm²
12 kVA 16 mm² 16 mm² 16 mm²
15 kVA 25 mm² 16 mm² 25 mm²
16 kVA 35 mm² 16 mm² (35 mm²)*