88 8-10 kVA, 50/60 Hz (1-phase input) &
8-15 kVA, 50/60 Hz (3-phase input)
P-164000341
User's Guide Revision 1
14 Technical data
Standards
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Safety IEC 62040-1-1, EN 62040-1-1 and EN 60950
EMC IEC 62040-2, IEC 60945
Product IEC 62040-3 and EN 62040-3
Approvals CE, DNV Type Approval, ABS Product Design Assess-
ment (Other classification survey reports on request)
Table 14-1: Standards
Environment
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Ambient
temperature
0 to +40°C (electronics), max. +45ºC with
7.5% derating 15 to +25°C (batteries)
Relative humidity 0 to 95%, no condensation allowed
Altitude < 1000m above sea level at +40°C, max. 2000m with 1% derating per +100m
Vibration IEC 60068-2-64 / DNV Class A; Endurance: Total RMS 1G (3-100 Hz)
Table 14-2: Environment
Mechanical configuration
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Width 335 mm
Depth 736 mm (Rear-mounted MBS: +108 mm)
Dimensions
Height 874 mm (2 modules) / 1272 mm (3 modules) (TA models: +86 mm)
No battery: 81 kg No battery: 105 kg
32 battery: 161 kg 32 battery: 161 kg
64 battery: 265 kg 64 battery: 265 kg
Weight
Transformer: 161 kg Transformer: 161 kg