7 Connection examples
7.3 Size 3 and 4 (41 – 200 A)
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 143
Figure 112: Actuation, motor cascade, part 1
a Enable
b Soft starter/Soft stop
c Starting frequency monitoring.
Set the timing relay so that the soft starter is not thermally overloaded.
The appropriate time relates to the admissible operating frequency of the selected soft starter.
Otherwise select the soft starter so that the required times are achievable.
d Set the timing relay to 2 s off-delay. This ensures that the next motor branch is not connected when a soft starter is running.
N/C contact S1 switches all motors off at the same time.
Figure 113: Actuation, motor cascade, part 2
a Motor 1
b Motor 2
c Motor n
The N/C contact S3 is required if motors also have to be switched off individually.