8 SmartWire-DT
8.9 Programming
178 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
8.9.3.10 Profile 10: Inputs (status)
Input bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.
Table 36: Profile 10: Input bytes 0 and 1
Byte
Bit Designation Meaning
0 0, 1 – Not used
2, 3 A1, A2 1-0-A switch on DS7:
00: not defined
10: Position A: Automatic (commands via
SmartWire-DT/control signal terminal)
01: Position 0: DS7 stop
11: Position 1: DS7 operation
4 DIAG 0: no diagnostic alarm
1: Diagnostic alarm present
5 – Not used
6 PRSNT 0: Device not present
1: Device present
7 SUBST 0: Configured module present
1: universal module M22-SWD-NOP(C) present
1
0 ERR Error present
0: no error
1: Error
1 WARN Warning present:
0: no warning
1: Warning
2 RDY Ready to operate, switched on
0: not switched on
1: switched on
3 RUN DS7 running, power section active
(DS7 Run, power part active):
0: Stop (power section inactive)
1: Operation (power section active)
4 TOR Top of ramp:
0: Top of start ramp not reached
1: Top of start ramp reached
5
1)
CL Current limit:
0: Current limit not reached
1: Current limit reached
6, 7 – Not used
1) Bit 5 will only be activated if parameter 681.0 is set to 1.