8 SmartWire-DT
8.9 Programming
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 179
8.9.3.11 Profile 10: Outputs (control)
Output bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.
Table 37: Profile 10: Output bytes 0 and 1
Byte 1 is only needed for internal SmartWire-DT-specific functions.
Byte Bit Designation Meaning
0
(Control
DS7)
0 EN_Set Enable Setpoint, DS7 Start/Stop:
EN_Set enables the setpoint value and starts or
stops the motor with the ramp function.
0: (deactivate setpoint value)
1: (activate setpoint value)
1 – Not used
2 EN_Op Operation released:
0: Stop (immediate disconnection of the output)
1: Operation
3 FaultAck Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0 → 1)
4 - 7 – Not used
1 0 - 7 – Not used