8 SmartWire-DT
8.9 Programming
180 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
8.9.3.12 Profile 11: Inputs (status)
Input bytes 0 to 4 are mapped as follows on SmartWire-DT.
Table 38: Profile 11: Input bytes 0 to 4
Byte Bit Designation Meaning
0 0, 1 Not used
2, 3 A1, A2 1-0-A switch on DS7:
00: not defined
10: Position A: Automatic (commands via
SmartWire-DT/control signal terminal)
01: Position 0: DS7 stop
11: Position 1: DS7 operation
4 DIAG 0: no diagnostic alarm
1: Diagnostic alarm present
5 Not used
6 PRSNT 0: Device not present
1: Device present
7 SUBST 0: Configured module present
1: universal module M22-SWD-NOP(C) present
1, 2 0 RSO Ready to switch on: S2
0: Not ready for switching on
1: Ready for switching on
1 RDY Ready to operate; switched on: S3
0: not ready for operation
1: ready for operation
2 EN Enabled: S4
0: Stop
1: Operation
3 ERR Error present (Error)
0: no error
1: Error
4 C_Stop Free run-down, output de-energized (coast stop)
0: no free run-down
1: free run-down
5 Q_Stop Quick stop, shortest ramp
0: no quick stop
1: Quick stop
6 SOI Switching On Inhibit: S1
0: No switch-on inhibit
1: Switch-on inhibit
7 WARN Warning present:
0: no warning
1: Warning
8 RUN DS7 run, power part active
0: Stop (power section inactive)
1: Operation (power section active)
9 Ctl_Req Control requested to PLC
Is set if PNU 928.0 = 1.
0: Not ready for remote control
1: Ready for remote control