8 SmartWire-DT
8.9 Programming
186 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
8.9.5.2 Acyclic DS7 soft starter data
The following table lists the various available parameters (PNUs). These
parameters are transmitted via the parameter channel described in the
following section.
PNU
Index
PNU
Sub-
index
Access
rights
Designation Data type Meaning Value range DS User
setting
Manufacturer Specific
11 0 rw U-Start N2 Start voltage 30 - 100 %
4915 - 16384
30 %
4915
11 1 ro U-StartPoti N2 Start voltage via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 11.0.
30 - 100 %
4915 - 11468
4915
12 0 rw U-StartEnd N2 U-start-end: The maximum ramp
voltage is reproduced here as a
percentage. Maximum reached:
100 %
30 - 100 %
4915 - 16384
100 %
16384
13 0 rw U-StopStart N2 U-stop-start: In the event of a soft
stop, the voltage will fall down to
the value set here; the stop ramp
will start
30 - 100 %
4915 - 16384
100 %
16384
14 0 rw U-Stop N2 U-Stop: Minimum ramp voltage
(end of soft stop), minimum
reached = 0 %
30 - 100 %
4915 - 16384
30 %
4915
111 0 rw t-Start T2 Start time 1 - 30 s
10 - 300
5s
50
111 1 ro t-Start-Poti T2 Start time via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 111.0.
1 - 30 s
10 - 300
–
112 0 rw TOR-Delay D2 Time between top of ramp and
TOR bit
150 - 400 ms
24576 - 65535
150 ms
24576
113 0 rw Stop-Delay D2 Stop delay:
Time between TOR and start of
stop ramp
150 - 400 ms
24576 - 65535
150 ms
24576
114 0 rw t-Stop T2 Stop Time 0 - 30 s
0 - 300
0s
0
114 1 ro t-StopPoti T2 Stop time via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 114.0.
0 - 30 s
0 - 300
–
202 0 ro Device Name OctetString DS7 designation – –
203 0 ro HW version Unsigned16 Hardware Version 0 - 65535 0
206 0 ro Firmware Version
(DS7-SWD)
Unsigned16 Firmware Version
(DS7-SWD)
0 - 65535 –