8 SmartWire-DT
8.9 Programming
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 187
210 0 rw I
m
Unsigned16 Rated motor current I
m
from
nameplate:
X = I
m
x 10
X = Read/written value
Example:
Rated motor current: 2, 3 A
Value that the PLC needs to send:
23
The value is used to calculate the
current limit (PNU 281.1).
It must be sent by the PLC if it is
different from the DS7’s rated
operational current I
e
. (I
e
is used
as a default setting.)
0 - 65535 0
280 0 ro I
e
Unsigned16 Soft starter rated operational
current I
e
:
X = I
e
x 10
X = Value read here
0 - 200 –
281 1 rw CurrentLimit Unsigned16 Current limitation:
A current limitation can be
implemented here by using a PKE.
If the configured limit value is
reached, the DS7-SWD will freeze
the voltage ramp and set the CL bit
in the SWD input byte (profiles 7,
to 9, and 11). PNU 681.0 activates
and deactivates the current
limitation. If the PKE does not
deliver any current, but PNU 681.0
= 1 and the DS7-SWD is running,
the DIAG2 bit will be set and, in
profiles 4 to 11, the WARN bit will
be set as well.
Rated motor current I
m
(PNU
210.0) is used for calculating the
current limitation within this
context. The value is independent
from the PKE motor-protective
circuit-breaker and from the DS7-
SWD soft starter model.
0 - 800 %
65535
300 %
24576
290 0 ro
rw
(version
V48 and
higher)
IeBreakerMax Unsigned16 Maximum current of PKE:
X = I
e
Breaker x 10
X = Value read here
I
e
= 21.7 A; X = 217
0 - 650 0
310 0 ro Profiles Unsigned16 Profile group being used
0: No selection
10: PROFIdrive profile
(Profiles 7, 8, 9, 11)
11: Short profile
(Profiles 4, 5, 6, 10)
12: Motor starter profile
(Profiles 1, 2, 3)
0 - 12 10
PNU
Index
PNU
Sub-
index
Access
rights
Designation Data type Meaning Value range DS User
setting