8 SmartWire-DT
8.9 Programming
188 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
362 0 rw ComLoss/Timeout T2 Time before automatic switch-off 10 - 300 10
514 1 ro IeBreaker Unsigned16 Current PKE current:
Corresponds to I_REL of the cyclic
input data with an expanded value
range
0 - 800 %
0 - 65535
0
681 0 rw SetCurrentLimit Unsigned8 Used to enable PKE current
limitation:
0: Current limitation deactivated
1: Current limitation activated
0; 1 0
723 0 ro OverloadStatus Unsigned8 Overload status:
0: No overload
1: Overload (main alarm)
0; 1 0
723 1 ro OverloadLimitStatus Unsigned8 Overload limit status:
The overload limit status is based
on PNU 823.1
0: Overload limit not reached
1: Overload limit reached
Potential impending overload fault
(Early-warning)
0; 1 0
750 0 ro InputStatusA1 Unsigned8 Current status of control signal
terminal A1:
0: Voltage unavailable
1: Voltage available
0 - 256
750 1 ro InputStatusEN Unsigned8 Current status of control signal
terminal EN:
0: Voltage unavailable
1: Voltage available
0 - 256
751 0 ro RelaisStatusTOR Unsigned8 TOR relay status:
0: not activated
1: activated
0 - 256 0
751 1 ro RelaisStatusRUN Unsigned8 RUN relay status:
0: not activated
1: activated
0 - 256 0
820 0 ro StartCounter Unsigned32 Counter for the number of starts 0 - (2
32
- 1)
821 0 ro RunTime T4 Service life counter (RUN):
Counts how long the DS7-SWD
soft starter is switched on (RUN)
0 - (2
32
- 1)
821 2 ro PowerOnTime T4 Mains voltage counter:
Counts how long mains voltage
(L1, L2, L3) is applied at the DS7-
SWD soft starter
0 - (2
32
- 1)
821 1 ro SupplyOnTime T4 Supply duration counter:
Counts how long control voltage
(24 V via terminal or SmartWire-
DT) is applied
0 - (2
32
- 1)
822 0 ro HeatsinkTemp Integer16 Heat sink temperature -255 - +255 °C
-32767 - 32767
0 °C
0
PNU
Index
PNU
Sub-
index
Access
rights
Designation Data type Meaning Value range DS User
setting

Table of Contents