8 SmartWire-DT
8.9 Programming
194 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Fire Mode
In normal operation each error message causes the soft starter to switch off.
If Fire mode is active, all protective functions can be disabled. In this case,
the soft starter will continue to run until it is ruined. Fire mode can be
activated by setting the error response to a value of “No response.”
Use parameter PNU 840 to do so. All the corresponding subindexes must be
set to 0.
The seven most recent faults will be stored in the device.
Fire mode can only be used when using profile 7, 8, 9, or 11.
In addition, bus monitoring must be enabled.
DANGER
Having Fire mode enabled will pose a risk of serious injury,
death, and property damage, as it will no longer be possible to
control the soft starter and the soft starter will remain active.