EasyManua.ls Logo

Eaton Pow-R-Line SPX0361126 - Digital Output (Relay Contact); Digital Input Card (-1)

Eaton Pow-R-Line SPX0361126
584 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.eaton.com IM02601001E 7-3
Using the I/O Option Cards

The Digital Output/Input card is a combination of relay contact outputs for load switching and dry/wet contact sensing
digital inputs. The outputs are electrically isolated from the inputs and from the main unit.


Power consumption: 0.320W internal
Relay outputs.
Number of outputs: 2
Contact type: Changeover (SPDT)
Relay type: Mechanically latching
Switching voltage: AC 250V / DC 30V
Switching power: 1250VA / 150W
Switching current: 5A
Switching rate max.: 10/s
Mechanical life: 5 x 10
7
switching operations
Electrical life: 10
5
switching operations at rated current
Breakdown voltage: AC 1000V between open contacts
Isolation: AC 3000V / 5000V surge system to contacts
Reset/Power down state: No change - last state is retained
Inputs.
Number of Inputs: 2
Sensing type: Wet or dry contact status detection
Wetting voltage: DC (12-24V), internally generated
Input current: 2.5mA – constant current regulated
Minimum input voltage: 0V (input shorted to common)
Maximum input voltage: DC 150V (diode protected against polarity reversal)
Filtering: De-bouncing with 50ms delay time
Detection scan rate: 100ms
Isolation: AC 2500V system to inputs

Operating temperature: (-20 to +70) °C
Storage temperature: (-40 to +80) °C
Relative air humidity: Maximum 95%, non-condensing
EMC - Immunity Interference: EN61000-4-2
Weight: 1.5oz
Dimensions (inch) W x H x L: 0.72 x 2.68 x 3.26
External Connection: AWG 12-26/(0.129 - 3.31)mm
2
9 pin, 0.200” pluggable terminal block