Electrical Data
NEMA
Size
Frame
Width
Ampere
Rating,
Continuous
Maximum Horsepower
Motor Voltage
60 Hz
1
φ 3 φ
00
45 mm
9
115
200
230
460
575
1
3
- - -
1
- - -
- - -
- - -
1
1
2
1
1
2
2
2
0
45 mm
18
115
200
230
460
575
1
- - -
2
- - -
- - -
- - -
3
3
5
5
1
65 mm
27
115
200
230
460
575
2
- - -
3
- - -
- - -
- - -
7
1
2
7
1
2
10
10
2
65 mm
45
115
200
230
460
575
3
- - -
7
1
2
- - -
- - -
- - -
10
15
25
25
3
90 mm
90
115
200
230
460
575
- - -
- - -
- - -
- - -
- - -
- - -
25
30
50
50
4
180 mm
135
115
200
230
460
575
- - -
- - -
- - -
- - -
- - -
- - -
40
50
100
100
5
180 mm
270
115
200
230
460
575
- - -
- - -
- - -
- - -
- - -
- - -
75
100
200
200
6
220 mm
540
115
200
230
460
575
- - -
- - -
- - -
- - -
- - -
- - -
150
200
400
400
7
280 mm
810
115
200
230
460
575
- - -
- - -
- - -
- - -
- - -
- - -
200
300
600
600
8
334 mm
1215
115
200
230
460
575
- - -
- - -
- - -
- - -
- - -
- - -
400
450
900
900
9
813 mm
2250
115
200
230
460
575
- - -
- - -
- - -
- - -
- - -
- - -
- - -
800
1600
1600
REFERENCE DATA
NEMA AN16 Starters — High Fault Current Circuit
Ratings — UL508
SCPD
Max
Rating
SCPD
(A)
Cir Bkr
Intrp
Rating
(KA)
Short
Circuit
Volt
(V)
Withstand
Current
(KA)
Typical
Disconnect
Size 00
Data To Be Available Later
Size 0
Class R, J Fuse
Mag Bkr — HMCP
Thrml Mag — FDC
60
30
35
100
100
100
600
480
480
100
100
100
C361
HMCP
FDC
Size 1
Class R, J Fuse
Mag Bkr — HMCP
Thrml Mag — FDC
60
30
90
100
100
100
600
480
480
100
100
100
C361
HMCP
FDC
Size 2
Class R, J Fuse
Mag Bkr — HMCP
Thrml Mag — FDC
100
50
150
100
100
100
600
480
480
100
100
100
C361
HMCP
FDC
Size 3
Class R, J Fuse
Mag Bkr — HMCP
Thrml Mag — FDC
200
150
150
100
100
100
600
480
480
100
100
100
C361
HMCP
FDC
Size 4
Class R, J Fuse
Mag Bkr — HMCP
Thrml Mag — JDC
400
150
250
100
100
100
600
480
480
100
100
100
400 A K SW
HMCP
JDC
Size 5
Class R, J Fuse
Mag Bkr — HMCP
Thrml Mag — KDC
600
600
400
100
100
100
600
480
480
100
100
100
600 A K SW
HMCP
FDC
Size 6
Class L Fuse
Class L Fuse
Thrml Mag — HLD
1200
1200
800
- - -
- - -
65
600
600
480
100
100
65
800 A K SW
MId Case N Fr
HLD
UL File E39943 — Issue Date 2/15/89.
UL File E47048 — Issue Date 11/23/87.
NOTE:
UL 508 STANDARD FAULT CURRENT RATINGS: All de-
vices are UL Listed with fuses and inverse time circuit breakers
to standard low level fault currents based on horsepower. All
AN16 starters conform. Sizes 00-3 to 5kA. Sizes 4-5 to 10kA.
Size 6 to 18kA. Size 7 to 30kA. Size 8 to 42kA and Size 9 to
85kA.
NEMA, Contactors & Starters, (Freedom)
Technical Information Publication
8231
Page 7
February 2, 1998

Table of Contents