RP01400001E For more information visit: www.eatonelectrical.com
Renewal Parts
Effective: February 2009 Page 35
Current Cutler-Hammer
Panelboards
PRL5P Chassis Layout
Figure 3. PRL5P Chassis Layout — Dimensions in Inches (mm)
If used as a main device, must be mounted at the neutral end of panel.
Fixed bus covers are required for unused spaces if NEC six circuit disconnect rule is to be met.
Blank wireway fillers are required opposite any dual breaker unit.
One “X” = 1.38 inches (35.1 mm).
6X
2-Pole
EHD, FD, FDB, HFD, FDC, ED, EDH, EDC
3-Pole
EHD, FD, FDB, HFD, FDC,
ED, EDH, EDC
2-Pole
EHD, FD, FDB, HFD,
FDC, ED, EDH, EDC
2-Pole
EHD, FD, FDB, HFD,
FDC, ED, EDH, EDC
Blank Wireway➂
3-Pole
FDB, EDH, HFD, FDC,
ED, EHD, EDC, FD
3-Pole
FDB, EDH, HFD, FDC,
ED, EHD, EDC, FD
Filler Plate
2- or 3-Pole
JD, HJD, JDC
2- or 3-Pole
DK, KD, HKD, KDB
Filler Plate
Neutral — No “X” Space Required
Top or Bottom
2-Pole
EHD, FD, FDB, HFD, FDC, ED, EDH, EDC
3-Pole
EHD, FD, FDB, HFD, FDC,
ED, EDH, EDC
Blank Wireway➂
2-Pole
EHD, FD, FDB, HFD,
FDC, ED, EDH, EDC
2-Pole
EHD, FD, FDB, HFD,
FDC, ED, EDH, EDC
Blank Wireway➂
2- or 3-Pole
HLD, LDC, LD
800A MDL, HMDL➀
Main or Branch
800A ND, HND, NDC➀
Main or Branch
1200A ND, HND, NDC➀
Main or Branch
Main Lug or Branch Lug Unit
600A, (2) 600 kcmil
800A, (3) 800 kcmil
1200A, (4) 750 kcmil
2X
3X
2X
2X
3X
4X
3X
3X
6X
6X
6X
7X
2X
3X
2X
2X
3X
4X
6X
6X
6X
7X
10
(254.0)
48
(1219.2)
10
(254.0)
10
(254.0)
2X
2X
3X
3X
3X
1X-6X
6X
4X
6X
8X
Neutral — No “X” Space Required
Top or Bottom
2-Pole
EHD, ED, EDH, EDC, FD, FDB, HFD, FDC
2-Pole
EHD, FD, FDB, HFD, FDC,
ED, EDC, EDH
2-Pole
EHD, FD, FDB, HFD, FDC,
ED, EDC, EDH
3-Pole
FDB, ED, HFD, FDC,
EHD, EDC, FD
3-Pole
FDB, ED, HFD, FDC,
EHD, EDC, FD
3-Pole
EHD, FD, FDB, HFD, FDC,
ED, EDH, EDC
2 or 3-Pole
JD, HJD, JDC
Bus Cover➁
2- or 3-Pole➀
DK, KD, HKD, KDB
Main or Branch
2- or 3-Pole➀
LD, HLD, LDC
Main or Branch
800A MDL, HMDL➀
Main Only
400A, 600A and 800A
Main Lug or Branch Lug➀
400A, (1) 750 kcmil or (2) 300 kcmil
600A, (2) 750 kcmil
800 (3) 600 kcmil
10
(254.0)
10
(254.0)
7
(177.8)
30
(762.0)
Single-Bus Interior in
30-inch (762.0 mm) Wide Enclosure
Double-Bus Interior Mounted in
48-inch (1219.2 mm) Wide Enclosure
10
(254.0)
10
(254.0)
➃