10-12 IM02601001E www.eaton.com
Setup on the Web Server Pages
SNMP Setup Edit Page
Option Cards
The PXM 2000 meter supports the following types of option cards:
Digital Output (Relay Contact) / Digital Input Card
Pulse Output (Solid State Relay Contacts) / Digital Input Card
1mA Output Card
20mA Output Card
Electrical specications and installation information for each card is covered in Chapter 7.

The Relay Output/Digital Input Option Card has:
Two relay contact outputs for load switching
Two wet/dry contact sensing digital inputs.
Accumulators in the software which count the transitions of the Inputs and Outputs.
A typical use of this card is to monitor the status of circuit breakers or relays.
Important: First use the  screen to set up the limits you want to
assign to an Output.
You can can use the  screen to congure up to eight limits. When
conguring this page, keep the following in mind:
Channel selects the electrical parameter through the  dialog box.
The various electrical measurements from the meter are grouped under the categories
of Demand, Reading, and Total Harmonic Distortion (THD).