EasyManua.ls Logo

Eaton Pow-R-Line SPX0361126 - Relay Output Setup Edit Page

Eaton Pow-R-Line SPX0361126
584 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-14 IM02601001E www.eaton.com
Setup on the Web Server Pages
Use the  page to set the output behavior of the relays. The
count reects the number of times the relay has energized. (You can dene the labels,
state names, operating delays, and congure the accumulator. The Divisor is a com-
pression factor for the accumulator, and you can select 1, 10, 100, 1000, 10000, and
100000. For example, if you choose a Divisor of 10, each time 10 state changes occur,
the accumulator count will increment by 1.
Relay Output Setup Edit Page

This option card has:
Four pulse outputs via solid state contacts.
Four wet/dry contact sensing digital inputs.
Accumulators in the software count the pulses of the Inputs and Outputs (the accumula-
tors are shown on the I/O page. Typically, this card is used in a sub-metering application
where a pulse output is needed. The (which perform the same func-
tion as the inputs on the relay card) allow you to count the pulses from another device, for
example, a KYZ module or another meter. The  allow you to count
the pulses being output by the card.
For inputs, you can congure up to four inputs for your card, and assign a , Open
, and  for each. You can also set labels and other in-
formation for  for the Inputs. Triggers can be set as Disabled, Open to
Close, Close to Open, or on .
Accumulators have both a compression factor and a device output ration setting. The
divisor is a compression factor for the accumulator, and you can select 1, 10, 100, 1000,
10000, and 100000. For example, if you choose a Divisor of 10, each time 10 state
changes occur, the accumulator count will increment by 1. The  is the
output ratio from the device that is being input into the meter. For example, if you have a
KYZ module that is outputting a pulse every 1.8 kWh, you would set the 
to be the value of the KYZ; in this case either 1.8 or a ratio of that number.
The Set Limit Channel dialog box associates a meter measure, like kW Demand or
Phase B current, with each of the outputs, and gets a pulse train whose rate reects the
present value of that measure.

Table of Contents

Related product manuals