www.eaton.com IM02601001E 10-3
Setup on the Web Server Pages
Quick Setup Page - Meter

The  page provides all of the TCP/IP communications settings.
You have two choices for conguring the meter:
Fixed (static) IP address
DHCP which resolves to a xed IP address
Eaton does not recommend using a DHCP setup that can randomly assign an IP address
from a pool of possible addresses. Rather, if you use DHCP you should use a scheme
wherein the router or layer 3 switch assigns a xed IP based on the MAC address of the
meter. Thus, at every reboot or power-up, the meter will always be granted the same IP
address. This method is sometimes called “static DHCP.”
Eaton recommends using a method that assigns a xed IP address for two reasons:
Software that may connect to and monitor the meter, such as Power Xpert Software,
accesses the meter via its IP address, and therefore if the meter losses power and
receives a new IP address on power-up, the connection from the software to the meter
will be broken.
Users will also generally navigate to the meter’s web pages via the meter’s IP ad-
dress. If the meter is assigned a different IP on power-up or reboot via DHCP, users
won’t know the new address and won’t be able to access the meter.
After you’ve assigned an IP address, it is visible from the front panel via the IP
menu.

Table of Contents