KS 3-2010
Page 8
Evidence of excessive high current switch closing operation includes:
Bright metal or metallic deposits on insulating surfaces or the enclosure interior
An excessive number of small, bright metal balls resting on the enclosure bottom end
wall
Excessive black film on insulating surfaces or the enclosure interior adjacent to the
contact air gap or arc chute exhaust
Enclosure shape distortion caused by excessive internal pressure
Contacts not fully engaging or closing
Rough mechanism operation
4.3.2.6 Reinstallation Procedure
For reinstallation or replacement of the switch and/or accessories, follow the installation safety
procedures given in 2.3 in conjunction with any installation instructions provided by the manufacturer.