www.eaton.com IM02601001E 6-9
Using the PXM 2000 Series

1. Press the Enter button when Cnct is in the A window. The Cnct screen appears.
2. Press the Right button or Down button to select a conguration.
The choices are:
• 3 Element Wye ()
• 2.5 Element Wye ()
• 2 CT Delta ()

earlier in this chapter.
3. When you have made your selection, press the Menu button twice.
4. The screen appears. Press Enter to save the setting. Use buttons to select conguration

Port conguration consists of :  (a three digit number), Baud Rate (9600; 19200; 38400; or 57600), and
Protocol (DNP 3.0; Modbus RTU; or Modbus ASCII).
1. Press the Enter button when POrt is in the A window.
The  (address) screen appears. You can either:
• Enter the address.
Access one of the other Port screens by pressing the Enter button: press Enter once to access the

screen (Baud Rate); press Enter twice to access the Prot screen (Protocol).
a.

Use the Down button to select the number value for a digit.
• Use the Right button to move to the next digit.
b.

Use the Right button or the Down button to select the setting you want.
c. 
Press the Right button or the Down button to select the setting you want.

2. When you have nished making your selections, press the Menu button twice.
3. The
 screen appears. Press Enter to save the settings.