www.eaton.com IM02601001E 10-15
Setup on the Web Server Pages
Digital Input Setup Edit Page
You can set up to four outputs for your card. You can dene the labels, state names, and
congure the accumulator. You can also specify the phase source and measurement.
Accumulators have both a compression factor and a device output ration setting. The
divisor is a compression factor for the accumulator, and you can select 1, 10, 100, 1000,
10000, and 100000. For example, if you choose a Divisor of 10, each time 10 state
changes occur, the accumulator count will increment by 1. The is the
output ratio from the device that is being input into the meter. For example, if you have a
KYZ module that is outputting a pulse every 1.8 kWh, you would set the 
to be the value of the KYZ; in this case either 1.8 or a ratio of that number.
Pulse Output Setup Edit