2-8 IM02601001E www.eaton.com
Overview and Specications
Compliance
UL Listing: USL/CNL E185559
CE (EN61326-1, FCC Part 15, Subpart B, Class A)
IEC 687 (0.2% Accuracy)
ANSI C12.20 (0.2% Accuracy)
ANSI C62.41 (Burst)
I C12.2 IEC 1000-4-2 - ESD
 (See full Range specications earlier in this chapter.)
For 23
o
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5A (Class 10)
nominal unit:
Parameter  
1
Voltage L-N [V] 0.1% of reading (69 to 480)V
Voltage L-L [V] 0.2% of reading
2
(120 to 600)V
Current Phase [A] 0.1% of reading
3
(0.15 to 5) A
Current Neutral (calculated)
[A]
2% of Full Scale (0.15 to 5) A @ (45 to 65) Hz
Active Power Total [W] 0.2% of reading

(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Active Energy Total [Wh] 0.2% of reading

(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Reactive Power Total [VAR] 0.2% of reading

(0.15 to 5) A @ (69 to 480) V @ +/- (0 to 0.8) lag/lead PF
Reactive Energy Total [VARh] 0.2% of reading

(0.15 to 5) A @ (69 to 480) V @ +/- (0 to 0.8) lag/lead PF
Apparent Power Total [VA] 0.2% of reading

(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Apparent Energy Total [VAh] 0.2% of reading

(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Power Factor 0.2% of reading

(0.15 to 5) A @ (69 to 480) V @ +/- (0.5 to 1) lag/lead PF
Frequency [Hz] +/- 0.03 Hz (45 to 65) Hz
Total Harmonic Distortion [%] +/- 2%
(0.5 to 10)A
4
or (69 to 480)V, measurement range (1 to 99.99)%
Load Bar +/- 1 segment (0.005 to 6) A
1
• For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
• For 1A (Class 2) Nominal, degrade accuracy by an additional 0.5% of reading.
• For 1A (Class 2) Nominal, the input current range for accuracy specication is 20% of the values listed
in the table.
2
For unbalanced voltage inputs where at least one crosses the 150V autoscale threshold (for example,
120V/120V/208V system), degrade the accuracy to 0.4% of reading.
3
With reference voltage applied (VA, VB, or VC). Otherwise, degrade accuracy to 0.2%. See hookup
diagrams 8, 9, and 10 in Chapter 4.
4 At least one voltage input (minimum 20 Vac) must be connected for THD measurement on current
channels.