EasyManua.ls Logo

Eaton Pow-R-Line SPX0361126 - Page 379

Eaton Pow-R-Line SPX0361126
584 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The information on this
document is created by Eaton
Corporation. It is disclosed
in confidence and it is only
to be used for the purpose in
which it is supplied.
PREPARED BY
EricSNims
DATE
04/29/13
APPROVED BY DATE
04/29/13
VERSION
7.9
NEG-ALT NUMBER
PX900719Y201-C001
REVISION DWG SIZE
A
Eaton Corporation
JOB NAME
Banner Health Centers
DESIGNATION
Panel X-Ray
TYPE
PRL1a
DRAWING TYPE
Final
G.O.
SPX0361126
ITEM
025I
SHEET
1 OF 1
12
34
56
78
910
11 12
13 14
15 16
17 18
BAB3040H BAB1020
BAB1020
BAB1020
BAB1020 PROV
PROV PROV
PROV PROV
PROV PROV
PROV PROV
PROV PROV
Main Breaker 60A
EHD3060, Vert Mtd.
Blank Cover
4 inches
General Information
(Section 1 of 1)
Service Voltage:
208Y/120V 3Ph 4W
Enclosure:
Type 1
Bus Rating & Type:
100A Copper
Neutral Rating:
100A
Ground Bar:
Std. Bolted Copper, Cu cable only
S.C. Rating:
10k A.I.C.Fully Rated
Main Device Type:
Main Breaker - Top Cable Entry
Main Terminals:
Mechanical - (1) #14-1/0 (Cu/Al)
Neutral Terminals:
Mechanical - (1) #14-1/0 (Cu/Al)
Box Catalog No.:
EZB2036R
Trim:
EZ Trim, Door in Door, Concealed Hardware (EZT2036F)
Flush Mounted
Box Dimensions:
36." [914.4mm]H x 20" [508.0mm]W x 5.75" [146.0mm]D
Min. Gutter Size:
Top = 5.5" [139.7mm] Bottom = 5.5" [139.7mm]
Left = 6.0" [152.4mm] Right = 6.0" [152.4mm]
Panel ID Nameplate: (1) Panel X-Ray
(2) 208Y/120V 3Ph 4W
(3) 60A MCB
Type:
Plastic, screw-on
Color:
White with Black Letters
NEC Lighting & Appliance, UL CTL ***Non-Interchangeable Main Device***
Branch Devices
Qty Poles Trip Frame Amps KAIC
1 3 40 BAB 100 10
4 1 20 BAB 100 10
11 1 PROV
Copper Neutral
Trim Lock:Standard Lock & Key (Keyed WEM2)
Circuit Directory:Metal Frame with Plastic Cover
Permanent Circuit Numbers
Main Circuit Breaker Trip Type: Thermal-Magnetic.
Do not connect breakers with combined ampere ratings that exceed 140 amperes
on any individual branch bus connector.
Device Modifications:
Ref # Description
Notes:

Table of Contents