Control Products Catalog CA08102001E—August 2010 www.eaton.com 13
33
33.1
NEMA Contactors and Starters
Freedom Series
Kits and Accessories
Auxiliary contacts,
contactor mounted—
Pages 2527
Transient suppressor, for
magnet coil—Page 24
Timers—solid-state and
pneumatic, mount on
contactor—Page 22
Renewal Parts
Publication Numbers
See Page 30
Technical Data and Specifications
Wire (75°C) Sizes—AWG or kcmil—NEMA Sizes 00–2—Open and Enclosed
Wire (75°C) Sizes—AWG or kcmil—NEMA Sizes 3–8—Open and Enclosed
Plugging and Jogging Service Horsepower Ratings
Notes
Minimum per NEC. Maximum wire size: Sizes 00 and 0 to 8 AWG and Sizes 1–2 to 2 AWG.
Two compartment box lug.
Maximum horsepower where operation is interrupted more than 5 times per minute, or more than 10 times in a 10 minute period.
NEMA Standard ICS2-1993 table 2-4-3.
NEMA Size Wire Size
Cu Only
Power Terminals—Line
00 12–16 AWG stranded, 12–14 AWG solid
0 8–16 AWG stranded, 10–14 AWG solid
1 8–14 AWG stranded or solid
2 3–14 AWG (upper) and/or 6–14 AWG (lower) stranded or solid
Power Terminals—Load—Cu Only (stranded or solid)
00–0 14–6 AWG stranded or solid
1–2 14–2 AWG stranded or solid
Control Terminals—Cu Only
12–16 AWG stranded, 12–14 AWG solid
NEMA Size Wire Size
Power Terminals—Line and Load
3 1/0–14 AWG Cu/Al
4 Open—3/0–8 AWG Cu; Enclosed—250 kcmil—6 AWG Cu/Al
5 750 kcmil—2 AWG; or (2) 250 kcmil—3/0 AWG Cu/Al
6 (2) 750 kcmil—3/0 AWG Cu/Al
7 (3) 750 kcmil—3/0 AWG Cu/Al
8 (4) 750 kcmil—1/0 AWG Cu/Al
Control Terminals—Cu Only
12–16 AWG stranded, 12–14 AWG solid
NEMA Size 200V 230V 460V 575V
00 1/2 1/2 1/2
0 1-1/2 1-1/2 2 2
13355
2 7-1/2 10 15 15
3 15203030
4 25306060
5 60 75 150 150
6 125 150 300 300