84
PROFIBUS-DP external communication cards
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Table 107. PROFIBUS parameters
Code Parameter Min. Max. Unit Default ID (Slot A/Slot B) Note
BX.1.1 Board Status 0 883/910 B0 = Optional Comm. Card Fault
B1 = Board HW Fault
B2 = Reserved
B3 = Fieldbus Fault
B4 = Reserved
BX.1.2 Firmware Version 1064/1066
BX.1.3 Protocol Status 0 2131/2142 0 = Waiting for Parameterization
1 = Parameterization Fault
2 = Waiting for Configuration
3 = Configuration Fault
4 = Data Exchange
BX.2.1 2 Slave Address 2 125 118 1242/1250 Address of the PROFIBUS Slave
BX.2.2 2 Baud Rate 1 10 10 1243/1251 Baud Rate for PROFIBUS
1 = 9.6 kBaud
2 = 19.2 kBaud
3 = 93.75 kBaud
4 = 187.5 kBaud
5 = 500 kBaud
6 = 1.5 MBaud
7 = 3 MBaud
8 = 6 MBaud
9 = 12 MBaud
10 = Automatic
BX.2.3 2 DO I/O Data 1 1 1 1244/1252 Drive Profile
1 = Standard Telegram
BX.2.4 2 Operation Mode 0 2 1 1245/1253 Operation Mode
0 = PROFIdrive
1 = Echo
2 = Bypass
BX.2.5 Comm Card FB
Fault Response
0 1 0 2519/2520 0 = In Fieldbus Control
1 = in all Control
ote:N X will depend on the slot the drive is in, Slot A = 7, Slot B = 14.
The parameters of every device must be set before connecting to the bus.
Especially the parameters “Slave Address” must be same as set in Master.