16
Modbus RTU On-Board communications
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Process data out 1 to 8
Process Data Out values 1 to 8 can be used in application for various purposes.
See below tables for additional information.
Process data OUT (slave → master)
The fieldbus master can read the AFD’s actual values
using process data variables. Standard, Pump and Fan
Control, PID control and Multi-Purpose applications use
process data as follows. These values are selectable via the
Fieldbus Process Data parameter group. These values would
correspond to the Modbus ID value. See Appendix A for
Parameter ID table showing values can be set.
Table 32. Process data OUT
Id Data Value Default value Default para Unit Scale
2104
Process Data OUT 1 -32768–32767 1 Output Frequency Hz
2105
Process Data OUT 2 -32768–32767 2 Motor Speed RPM
2106
Process Data OUT 3 -32768–32767 3 Motor Current A
2107
Process Data OUT 4 -32768–32767 4 Motor Torque %
2108
Process Data OUT 5 -32768–32767 5 Motor Power %
2109
Process Data OUT 6 -32768–32767 6 Motor Voltage V
2110
Process Data OUT 7 -32768–32767 7 DC Link Voltage V
2111
Process Data OUT 8 -32768–32767 28 Latest Fault Code —
Process data IN (master → slave)
Control Word, Reference and Process Data are used with All-in-One applications as follows.
Table 33. Process data IN
ID Data Value Unit Scale
2003
Reference Speed Reference Hz 0.01
2001
Control Word — — —
2004
Process Data IN1
% 0.01%
2005
Process Data IN2
% 0.01%
2006
Process Data IN3
% 0.01%
2007
Process Data IN4
% 0.01%
2008
Process Data IN5
% 0.01%
2009
Process Data IN6
% 0.01%
2010
Process Data IN7
% 0.01%
2011
Process Data IN8
% 0.01%
ote:N
Process Data IN1 through Process Data IN8 change
based off the selected application. See Appendix B
forlayout.
Startup test
Select Fieldbus (Bus/Comm) as the active control and
reference place.
1. Set FB control word (Modbus Address 42000) value
to1hex
2. DG1 status is RUN
3. Set FB Speed reference (Modbus Address 42002) value
to 5000 (= 50.00%)
4. The Actual value is 5000 and the DG1 output frequency
is 50.00%
5. Set FB control word (Modbus Address 42000) value
to0hex
6. DG1 status is STOP