Modbus RTU On-Board communications
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Process data in
This register range is reserved for the control of the VFD. Process Data In is located in range ID 2001–2099. The registers are
updated every 10 ms. See table below.
Table 23. Fieldbus basic input table
ID Modbus register Group Range/Type ID Modbus register Group Range/Type
2001 32001, 42001
FB Control Word Binary coded
2007 32007, 42007
FB Process Data In 4 Integer 16
2002 32002, 42002
FB General Control Word Binary coded
2008 32008, 42008
FB Process Data In 5 Integer 16
2003 32003, 42003
FB Speed Reference 0100.00%
2009 32009, 42009
FB Process Data In 6 Integer 16
2004 32004, 42004
FB Process Data In 1 Integer 16
2010 32010, 42010
FB Process Data In 7 Integer 16
2005 32005, 42005
FB Process Data In 2 Integer 16
2011 32011, 42011
FB Process Data In 8 Integer 16
2006 32006, 42006
FB Process Data In 3 Integer 16
ote:N For FB Process Data In, see section below on Process Data IN.
Control word
PowerXL DG1 drive uses 16 bits as shown below. These bits are application specific.
Table 24. Binary bits and corresponding outputs
15 14
13 12 11 10 9 8 7 6 5 4 3 2 1 0
FB Ref FB Ctrl Bypass FB DI 4 FB DI 3 FB DI 2 FB DI 1 Fault Reset Reverse RUN
ote:N
The bit is not used.
Table 25. FB control word
Bit
Description
Value = 0 Value = 1
0 Drive Output Off
Drive Output On
1 Clockwise Rotation
Counter Clockwise
2 No Reset
Fault Reset
3 FB INDATA1 Off
FB INDATA1 On
4 FB INDATA2 Off
FB INDATA2 On
5 FB INDATA3 Off
FB INDATA3 On
6 FB INDATA4 Off
FB INDATA4 On
7 Bypass Relay Disable
Bypass Relay Enable
8 FB Control Off
FB Control On
9 FB Reference Off
FB Reference On
10–15 Not in use
Not in use
Fb general control word
The DG1 does not use the FB General Control Word.
The main control word is used to provide commands to
thedrive.
Table 26. Speed reference
15 14
13 12 11 10 9 8 7 6 5 4 3 2 1 0
MSB
LSB
This is the Reference 1 to the VFD. Used normally as Speed
reference.
The scaling on this value is 0–100.00% of the Maximum
Frequency (P1.2). The 0 to 100.00% is represented by 0 to
10,000 value indicating 0 or 0% as Minimum Frequency
(P1.1) and 10,000 or %100.00 as Maximum Frequency
(P1.2). This value has 2 decimal places in it.
Process data in 1 to 8
Process Data In values 1 to 8 can be used in applications for
various purposes. See Process Data IN section for setup.