CANopen external communication cards
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Fixed control word
Table 147. Fixed control word
Bit Name
0 Run
1 Counterclockwise
2 Rising edge of this bit will reset active fault
3 FB Input data 1
4 FB Input data 2
5 FB Input data 3
6 FB Input data 4
7 Bypass
8 FB_Ctrl
9 FB_Ref
10 Not in use
11 Not in use
12 Not in use
13 Not in use
14 Not in use
15 Not in use
Bit
Description
Value = 0 Value = 1
0 Stop RUN
1 Clockwise Counterclockwise
2 Rising edge of this bit will reset active fault Rising edge of this bit will reset active fault
3 FB Input data 1 off FB Input data 1 On
4 FB Input data 2 off FB Input data 2 On
5 FB Input data 3 off FB Input data 3 On
6 FB Input data 4 off FB Input data 4 On
7 Switch to drive Switch to bypass
8 Control of drive is not selected from fieldbus Control of drive is selected from fieldbus
9 Reference is not selected from fieldbus Reference is selected from fieldbus
10–15 Not in use Not in use
Speed ref percentage
The Speed Reference Percentage is based off a 0 to 100.00 %(10000) scale with
0 being 0 rpm and 10000 indicating 100.00% speed value. A negative value will
indicate the inverted direction.
Process data in
The Process Data In values are based off the application selected. See Appendix B
to reference the current Process Data In values assigned.