167
Appendix B—Process data values
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Appendix B—Process data values
Process data OUT (slave master)
The fieldbus master can read the frequency converter’s actual values using process data variables. All software applications
use process data as follows:
Table 189. Process data OUT (slave master)
Data Value Unit Scale Default, Min., Max.
Process data out 1 Output frequency Hz 0.01 Hz
Process data out 2 Motor dpeed rpm 1 rpm
Process data out 3 Motor current A 0.1 A
Process data out 4 Motor torque % 0.10%
Process data out 5 Motor power % 0.10%
Process data out 6 Motor voltage V 0.1 V
Process data out 7 DC link voltage V 1 V
Process data out 8 Latest fault code
ote:N The communication parameter group in any application has a selector parameter for every process data.
The monitoring values and drive parameters can be selected using the ID number. Default selections are shown in the
table above. Reference Appendix A for Modbus IDs that can be set via the keypad P20.1 FB Process Data Out group.