Modbus TCP On-Board communications
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
FB control word
PowerXL DG1 drive uses 16 bits as shown below. These bits are application specific.
Table 54. Binary bits and corresponding outputs
15 14
13 12 11 10 9 8 7 6 5 4 3 2 1 0
FB Ref FB Ctrl BYS FB DIN 4 FB DIN 3 FB DIN 2 FB DIN 1 F_RST DIR RUN
ote:N
The bit is not used.
FB general control word
The DG1 does not use the FB General Control Word. The
main control word is used to provide commands to the drive.
Table 55. FB control word
Bit
Description
value = 0 Value = 1
0 Drive Output Off
Drive Output On
1 Clockwise Rotation
Counter Clockwise
2 No Reset
Fault Reset
3 FB INDATA1 Off
FB INDATA1 On
4 FB INDATA2 Off
FB INDATA2 On
5 FB INDATA3 Off
FB INDATA3 On
6 FB INDATA4 Off
FB INDATA4 On
7 Bypass Relay Disable
Bypass Relay Enable
8 FB Control Off
FB Control On
9 FB Reference Off
FB Reference On
10–15 Not in use
Not in use
Table 56. Speed reference
15 14
13 12 11 10 9 8 7 6 5 4 3 2 1 0
MSB
LSB
This is the Reference 1 to the VFD. Used normally as Speed
reference.
The scaling on this value is 0–100.00% of the Maximum
Frequency (P1.2). The 0 to 100.00% is represented by
0to10,000 value indicating 0 or 0% as Minimum Frequency
(P1.1) and 10,000 or %100.00 as Maximum Frequency
(P1.2). This value has 2 decimal places in it.
Process data in 1 to 8
Process Data In values 1 to 8 can be used in applications for
various purposes. See below Process Data IN section
for setup.