115
CANopen external communication cards
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Fixed Status Word
Table 148. Fixed status word
Bit Name
0 Ready
1 RUN
2 Counterclockwise
3 Faulted
4 Warning
5 Ref. Frequency reached
6 Bypass
7 Run enable
8 Not in use
9 Not in use
10 Not in use
11 Not in use
12 Not in use
13 Not in use
14 Not in use
15 Not in use
Bit
Description
Value = 0 Value = 1
0 Not Ready Ready
1 STOP RUN
2 Clockwise Counterclockwise
3 — Faulted
4 — Warning
5 Ref. frequency not reached Ref. Frequency reached
6 — Motor is running in bypass
7 Disable motor run Enable motor run
8–15 Not in use Not in use
Actual speed percentage
The Actual Speed Percentage indicates the actual speed
value of the motor. This value will be read as a 0 to
10000value, which indicates 0 to 100.00% speed actual.
FB process data out
The Process Data Out value is assigned by the Fieldbus
Parameter group in the application parameters. These
8values can be set to any available Modbus ID value listed.
See Appendix B to reference the default Process Data Out
values assigned.