74
BACnet MS/TP—On-Board communication
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
BACnet overview
BACnet technical data
Protocol Implementation Conformance Statement (PICS)
Controller Profile
•
B-ASC
Segmentation Capability
•
Not supported
Data Link Layer and Routing Options
•
MS/TP Master Baud rates
(9600,19200,38400, 76800, 115200)
Character Sets Supported
•
UTF8
BIBBS Supported
•
Data Sharing
• ReadProperty-B
• WriteProperty-B
•
Device Management
• Dynamic Device Binding–B
• Dynamic Object Binding–B
• DeviceCommunicationControl–B
• ReinitializeDevice–B
•
Alarms and Events: Not supported
•
Schedules: Not supported
•
Trends: Not supported
•
Network Management: Not supported
Table 98. Supported object types and properties summery
Property
Device
object type
Analog value
object type
Binary value
object type
Object_identifier
Object_name
Object_type
System_status
— —
Vendor_name
— —
Vendor_identifier
— —
Model_name
— —
Firmware_revision
— —
Application_software_version
— —
Location — — —
Description
Protocol_version
— —
Protocol_revision
— —
Protocol_services_supported
— —
Protocol_object_types_supported
— —
Object_list
— —
Structured_object_list — — —
Max_apdu_length_accepted
— —
Segmentation_supported
— —
Vt_classes_supported — — —
Active_vt_sessions — — —
Local_time — — —
Local_date — — —
Utc_offset — — —
Daylight_savings_status — — —
Apdu_segment_timeout — — —