168
Appendix B—Process data values
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Process data IN (master → slave)
Control word, Reference and Process Data are used with All-in-One applications as follows:
Table 190. Process data IN (master → slave)
Application
data
Standard and multi-pump
palue Data type Unit Scale Default
Reference Speed reference UINT % 0.01% 0
FBFixedControlWord Start/Stop/Fault reset command UINT — — —
PD1 – PD7 Not used UINT — — —
PD8 Analog output UINT — — —
Application
Data
Multi-purpose control
value Data type Unit Scale Default
Reference Speed reference UINT % 0.01% 0
FBFixedControlWord Start/Stop/Fault reset command UINT — — —
Process data IN1 Torque reference UINT % 0.10% 0
Process data IN2 Reference for PID1 controller UINT % 0.01% 0
Process data IN3 Actual value 1 to PID1 controller UINT % 0.01% 0
Process data IN4 Actual value 2 to PID1 controller UINT % 0.01% 0
Process data IN5 Reference for PID2 controller UINT % 0.01% 0
Process data IN6 Actual value 1 to PID2 controller UINT % 0.01% 0
Process data IN7 Actual value 2 to PID2 controller UINT % 0.01% 0
Process data IN8 Analog output UINT % 0.01% 0
Application
data
PID Control
value Data type Unit Scale Default
Reference Speed reference UINT % 0.01% 0
FBFixedControlWord Start/stop/fault reset command UINT — — —
Process data IN1 Not used UINT — — —
Process data IN2 Reference for PID1 controller UINT % 0.01% 0
Process data IN3 Actual value 1 to PID1 controller UINT % 0.01% 0
Process data IN4 Actual value 2 to PID1 controller UINT % 0.01% 0
Process data IN5 Reference for PID2 controller UINT % 0.01% 0
Process data IN6 Actual value 1 to PID2 controller UINT % 0.01% 0
Process data IN7 Actual value 2 to PID2 controller UINT % 0.01% 0
Process data IN8 Analog output UINT % 0.01% —
To change the Application, go into the P21.1.2 Application to
adjust the desired All-in-One application.