67
EtherNet/IP On-Board communications
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Assembly instance 117
Table 94. Instance 117 (input). EIP drive status length = 34 bytes
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 CtrlFromNet At zero speed AtReference Alarm/Warning Faulted Direction Running Ready
1 NA
2
% Speed actual (Low Byte)
3
% Speed actual (High Byte)
4
RPM speed actual (Low Byte)
5
RPM speed actual (High Byte)
6 Reserved
7 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
16 Reserved
17 Reserved
18 ProcessDataOut1 (LowByte)
19 ProcessDataOut1 (HighByte)
20 ProcessDataOut2 (LowByte)
21 ProcessDataOut2 (HighByte)
22 ProcessDataOut3 (LowByte)
23 ProcessDataOut3 (HighByte)
24 ProcessDataOut4 (LowByte)
25 ProcessDataOut4 (HighByte)
26 ProcessDataOut5 (LowByte)
27 ProcessDataOut5 (HighByte)
28 ProcessDataOut6 (LowByte)
29 ProcessDataOut6 (HighByte)
30 ProcessDataOut7 (LowByte)
31 ProcessDataOut7 (HighByte)
32 ProcessDataOut8 (LowByte)
33 ProcessDataOut8 (HighByte)
This is the actual value from the frequency converter. The value is between 0 and 10000. In the application, the value is scaled
in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%0000 = 100.00%).
The RPM Speed Actual is the actual speed of the motor. The unit is RPM.
ote:N See Appendix B for Process Data Value defaults.