7 Defining system parameters
7.2 InitPLC file with default parameters
100 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
#-----------------------------------------------------------
# Bootproject behaviour
#-----------------------------------------------------------
# A bootproject can be copied form a distant location to "/home/Plc_Prg"
and started as bootproject.
# the check for bootprojects will terminate at the first location a boot-
project is found.
# Test order: SD-Card, USB-Stick, User defined path.
# Overwrite existing bootproject if it differs to the one found on the
external location.
OVERWRITE_BP=1
# Set to 1 to copy a bootproject from "/home/disk_sd/XC303/Project" to
local storage "./Plc_Prg"
COPY_BOOTPROJECT_FROM_SD=1
# Set to 1 to copy a bootproject from "/home/disk_usb/XC303/Project" to
local storage "./Plc_Prg"
COPY_BOOTPROJECT_FROM_USB=1
# Set to 1 to copy a bootproject from a defined path
(USER_DEFINED_BP_PATH) to local storage "./Plc_Prg"
COPY_BOOTPROJECT_FROM_USER_DEFINED_BP_PATH=0
USER_DEFINED_BP_PATH=
# A bootproject located on the plc will be deleted if a file named
"deletebootapplication" is found on an
# USB or SD folder /XC303/update
ALLOW_BOOTPROJECT_DELETION=1
#-----------------------------------------------------------
# Firmware update behaviour
#-----------------------------------------------------------
# Update firmware only if the version of the image to be updated is higher
than the existing firmware.
FW_ONLY_NEWER_VERSION=0
# Overwrite existing firmware in any case. Flag will be removed on first
firmware-update
FW_FORCED_OVERWRITE=0
# Take firmware from SD card "/home/disk_sd/XC303/Firmware"
FW_INSTALL_FROM_SD=1
# Take firmware from USB-storage "/home/disk_usb/XC303/Firmware"
FW_INSTALL_FROM_USB=1
# Set to 1 to install a firmware XSoft-Codesys Updater"
FW_INSTALL_FROM_XSOFTCODESYS=1
# Set to 1 to install a firmware from a defined path
(USER_DEFINED_FW_PATH)"
FW_INSTALL_FROM_USER_DEFINED_FW_PATH=0
USER_DEFINED_FW_PATH=
#-----------------------------------------------------------
# Reset network settings
#-----------------------------------------------------------
# You should take care to move the networkconf file, once the reset values
have been applied.
# A networkconf template file can be found on /home/etc/network-
config.templ
# Reset network configuration by booting the plc with a config File
located on /home/disk_usb/XC303/update/networkconfig
NW_UPDATE_FROM_USB=1
# Reset network configuration by booting the plc with a config File
located on /home/disk_sd/XC303/update/networkconfig
NW_UPDATE_FROM_SD=1