6 In-/output configuration and parameterization
6.1 Configuring the device's local inputs/outputs
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 93
6 In-/output configuration and parameterization
6.1 Configuring the device's local inputs/outputs
The I/Q1 to I/Q4 local inputs/outputs of the PLC are configured as inputs by
default. If you want to change this configuration, follow the steps below:
▶ Select the device in the configuration tree and double-click to open the
"Device" tab.
▶ Select "LOCAL_IO Parameter".
▶ Double-clicking on a cell in the "Value" column will show a drop-down
menu that you can use to define the node as an input, output, or inter-
rupt input.
Figure 67: Configuration of the inputs/outputs