10 EtherCAT
10.2 Configuring the EtherCAT master
118 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
Figure 84: Device tree with EtherCAT master
10.2 Configuring the EtherCAT master
Double-click on "EtherCAT_Master (EtherCAT Master)" in the PLC config-
uration device tree.
Click on the <Search> button in the "General" tab.
Figure 85: EtherCAT master parameters
XSOFT-CODESYS-3 will show the MAC addresses and names for the Ether-
net interfaces on the XControl PLC.
Figure 86: List of all XC-303-C32-002 PLC Ethernet interfaces found
Select the Ethernet port to which you connected or will be connecting
the EtherCAT gateway.
Select the "Select network by name" setting in the "General" tab. This will
make the PLC connect by name (e.g., "ETH2") independently of the MAC
address.
Enable the "Automatic slave restart" option so that communication with
the modules will start automatically.