7 Defining system parameters
7.3 Switch-on of the control with inserted memory card with InitPLC file
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 101
7.3 Switch-on of the control with inserted memory card with InitPLC file
These system parameters are also active after a new program is loaded.
The start process will update the following:
Firmware
Boot project (user program)
Network configuration
See also Section “3.3 Startup behavior XC-104-…, XC-204-…, XControl”,
page 56.
For all checks in general after the Modular PLCs XControl: XC-104-…, XC-
204-…, XC-303-… start, the MicroSD slot will be checked first and then the
USB Host!
#-----------------------------------------------------------
# Start behaviour
#-----------------------------------------------------------
# Delay the start of the runtime system for a given number of seconds.
# (This start delay may be needed to detect USB devices.)
PLC_START_DELAY_SEC=4
# Set to 1 to skip the plc-runtime start
DISABLE_PLC_START=0
# Restrict the processor core usage of the plc-runtime. Valid entries:
"CORE_0", "CORE_1", "BOTH"
PLC_CORE_USAGE=CORE_1
# Set to 1 to constantly check rts-state.
PLC_SUPERVISE_RTS=1
# Set to 1 to Reboot the PLC if the runtimesystem terminates unexpectedly.
PLC_REBOOT_ON_RTS_TERMINATION=1
#-----------------------------------------------------------
# Log Files
#-----------------------------------------------------------
# Defined path used to safe log files.(Default path "/var/log" is vola-
tile,
# log files located there are lost after a power cycle.)
LOGFILE_DIR=/var/log
# Name of log file containing messages during the start up process.
LOGFILE_STARTUP=XC303Log.txt
# Name of log file containing messages from the plc runtime system.
LOGFILE_RTS=codesyscontrol.log
#-----------------------------------------------------------
# Map network drive
#-----------------------------------------------------------
# A network drive may be mapped into the view of the plc filesystem using
nfs (Linux/Unix) or cifs (Windows).
# Using nfs (network file system). A path "/home/disk_nfs" will be
created.
MAP_NFS_FOLDER=0
NFS_SOURCE_PATH=
# Using cifs (common internet file system). A path "/home/disk_cifs" will
be created
MAP_CIFS_FOLDER=0
CIFS_SOURCE_PATH=
CIFS_USER_NAME=
CIFS_DOMAIN_NAME=
CIFS_PASSWORD=