2 Installation
2.4 Connection terminals
38 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
Figure 25: Disassembling the system block
2.4 Connection terminals
Plug connector
X1 – Xn: The plug connectors with spring-loaded push-in terminals are
included as standard with the Modular PLCs XControl: XC-104-…, XC-204-…,
XC-303-….
Connecting cable
To use them, the conductor simply needs to be slid into the appropriate con-
tact and will be locked into place.
In order to release the conductor, simply press on the release mechanism,
e.g., with a screwdriver, to pull out the conductor from the corresponding
contact.
Table 7 Connection specifications
→
Only use copper cables designed for at least 90°C as the con-
necting cable.
Cable cross-sectional areas XControl
10 mm (0.39“) solid mm
2
0.2 – 1.5
10 mm (0.39“) Flexible with uninsulated
ferrule
mm
2
0.2 – 1.5
10 mm (0.39“) Flexible with insulated ferrule mm
2
0.2 – 0.75
Ferrule d mm
≤ 2.8
AWG
24 – 16
Strip length mm 10